P3001 - 1-5/8" x 2 3/4", 12 Gage, Back-to-Back, Solid

0
0 review(s) | Add your review
Elements of Section - P3001

Area of Section
1.000 in2 (6.5 cm2)
Axis 1-1
Axis 2-2
Moment of Inertia (I)
0.591 in4 (24.6 cm4)
0.407 in4 (16.9 cm4)
Section Modulus (S)
0.430 in3 (7.0 cm3)
0.501 in3 (8.2 cm3)
Radius of Gyration (r)
0.769 in (2.0 cm )
0.638 in (1.6 cm )
Column Loading -
P3001

Unbraced
Height
(in)

Allowable
Load at

Slot Face
(lbs)

Max Column Load
Applied at C.G.
K=0.65
(lbs)
K=0.80
(lbs)

K=1.0
(lbs)

K=1.2
(lbs)

24

5,74021,78021,20020,43019,720

36

5,62020,52019,72018,83017,680

48

5,52019,40018,57016,57014,260

60

5,33018,51016,57013,67010,810

72

5,03016,85014,26010,8107,730

84

4,63014,99011,9308,1805,680

96

4,19013,0909,7206,2604,350

108

3,72011,2307,7304,950*

120

3,3009,4606,2604,010*

144

2,6206,5904,350**
*KL/r > 200
Beam Loading - P3001
Span
(in)
Max
Allowable

Uniform
Load
(lbs)

Defl at
Uniform
load

(in)

Uniform Loading
at Deflection
Lateral
Bracing
Reduction

Factor

Span
/180
(lbs)
Span

/240
(lbs)

Span
/360
(lbs)
24*2,9600.03*2,960*2,960*2,9601.00
362,4000.082,4002,4002,4001.00
481,8000.151,8001,8001,6101.00
601,4400.231,4401,4401,0300.98
721,2000.331,2001,0807200.95
841,0300.461,0307905300.92
969000.598106104000.88
1088000.756404803200.85
1207200.935203902600.82
1446001.343602701800.76
1685101.812602001300.70
1924502.382001501000.64
2164003.01160120800.58
2403603.72130100-0.52
*Load limited by weld shear

Notes:

  1. Above loads include the weight of the member. This weight must be deducted to arrive at the net allowable load the beam will support.
  2. Long span beams should be supported so as to prevent rotation and twist.
  3. Allowable uniformly distributed loads are listed for various simple spans, that is, a beam on two supports. If load is concentrated at the center of the span, multiply load from the table by 0.5 and corresponding deflection by 0.8.
  4. The lateral bracing factor should be multiplied by the load to determine the load retained based on the distance between lateral braces.

Bearing Load on Channel:

Max Load
5,000 Lbs2,268 Kg
Max Load
8,000 Lbs3,629 Kg
Max Load
3,500 Lbs1,588 Kg

1-5/8" Series Channel:
Material:

  • Unistrut channels are accurately and carefully cold formed to size from low-carbon strip steel.
  • All spot-welded combination members, except P1001T, are welded 3" (76 mm) maximum on center.
  • Steel: Plain 12 Ga. (2.7 mm), 14 Ga.(1.9 mm) and 16 Ga. (1.5 mm); ASTM A1011 SS GR 33.
  • Steel: Pre-Galvanized 12 Ga. (2.7 mm), 14 Ga. (1.9 mm) and 16 Ga. (1.5mm); ASTM A653 GR 33.

Dimensions:

  • Imperial dimensions are illustrated in inches. Unless noted, all metric dimensions are shown in millimeters.

Curved Channel:

  • Many Unistrut 1-5/8" (41mm) channel sections are available as curved pieces in both single and combination styles.
    Contact your local Unistrut Service Center or Unistrut Corporation for ordering information.

Standard Lengths:

  • Standard lengths are 10 feet (3.05m) and 20 feet (6.10m). Tolerances are ±1/8" (3 mm) to ±1/2" (13 mm) to allow for cutting.
    Special lengths are available for a small cutting charge with a tolerance of ±1/8" (3 mm).

Load Data:

  • All beam and column load data pertains to carbon steel and stainless steel channels. Load tables and charts are constructed to be in accordance with the SPECIFICATION FOR THE DESIGN OF COLD-FORMED STEEL STRUCTURAL MEMBERS 2001 EDITION published by the AMERICAN IRON AND STEEL INSTITUTE USING ASD METHOD.

1-1/4" Series Channel:

Application:

  • A framing system designed for medium loads, the 1-1/4" series is especially suitable for use in the OEM, commercial and display markets. It maintains a lightness in scale and a clean line that makes it aesthetically pleasing as well as functional.

Material:

  • Steel: Plain
    14 Gauge (1.9 mm), ASTM A1011 SS GR 33
    19 Gauge (1.0 mm) ASTM A1008

  • Steel: Pre-Galvanized
    14 Gauge (1.9 mm), ASTM A653 GR 33

    19 Gauge (1.0 mm) ASTM A653 GR 33

13/16" Series Channel:

Application:

  • A unique half-size reduction of the 1-5/8" channel width series, this smaller channel size can be used to carry light loads economically in applications such as instrumentation, retail displays and light-duty laboratory supports. It also provides the flexibility found in all Unistrut® framing systems.

Standard Lengths:

  • P-6000 – 16 Feet (4.88m)
  • P-7000 – 10 Feet (3.05m)

Material:

  • Steel: Plain
    19 Gauge (1.0 mm) ASTM A1008

  • Steel: Pre-Galvanized
    19 Gauge (1.0 mm) ASTM A653 GR 33

More than 200 pages to explore

Unistrut metal framing channel, fasteners and hardware are the materials of choice for OEMs, contractors and plant maintenance personnel. Download the catalog to learn more.

1.jpg